Fire systems in NMR rooms (summary)

From: Carlos Amezcua <camezcua_at_biochem.swmed.edu>
Date: Thu, 06 Nov 2003 09:54:05 -0600

It seems that the options with respect to fire prevention systems are
limited by the existing local fire regulations and cost. Below is a list
of some of the systems commonly used by NMR labs:

1) Conventional Sprinklers: In this case, the recommendation is to avoid
  sprinkler heads on top of magnets and consoles as well as raising the
UPSs from the floor.

2) Pre-action sprinkler systems (also known as "dry" sprinklers). These
systems are also used in computer rooms. The sprinkler lines are
pressurized with air, and in the event of a fire, the sprinkler head is
activated as usual by heat, the air pressure in the pipes is released,
and a valve opens to allow water to flow to the sprinkler head as in a
normal system.
        When using this systems, it is recommended to locate the smoke
detectors in the return air ducts so that the system does not activate
with a quench. Genuine smoke will get into the return air ducts but the
helium from a quench will dissipate before it gets to the detector. A
recommended vendor was Wayman Fire Systems.

3) One no-water alternative is the so called FM 200 systems. This is a
gas-based fire systems using "Halon" and apparently has potential health
and safety hazard issues. In addition, the cost of th FM 200 is in the
$40-50K.

4) Non-magnetic Halon or CO2 extinguishers.

5) An interesting option, used by some in Europe, is to build fire proof
buildings made out of concrete and/or bricks and non-flamable materials
like wood.

        I hope this information help everyone involve in designing or planing
NMR facilities.

Best regards,

Carlos

-- 
Dr Carlos A. Amezcua
NMR Facility Manager
Department of Biochemistry
University of Texas Southwestern Medical Center
5323 Harry Hines Blvd.
Dallas, TX 75390-9038
Tel: (214) 648-8964
Received on Thu Nov 06 2003 - 16:11:40 MST

This archive was generated by hypermail 2.4.0 : Wed Jun 07 2023 - 17:14:43 MST